S2 Protection; Description; Standard Overload Curves - GE MOTOR MANAGER 2 Instruction Manual

Hide thumbs Also See for MOTOR MANAGER 2:
Table of Contents

Advertisement

4.3 S2 PROTECTION

4.3 S2 PROTECTION
This page is used to enter all information about the protection of the motor and the load. Setpoints
Page 2 is divided into four sections, MOTOR PROTECTION THERMAL, MOTOR PROTECTION
GROUND FAULT, MOTOR PROTECTION OPTIONS, LOAD PROTECTION and UNDER/OVER-
VOLTAGE PROTECTION.
Table 4–1: STANDARD OVERLOAD CURVE TRIP TIMES (IN SECONDS)
OVERLOAD
LEVEL
1.05
7200
1.10
4
1.20
1.30
1.40
1.50
1.75
2.00
2.25
2.50
2.75
3.00
3.50
4.00
4.50
5.00
5.50
6.00
6.50
7.00
7.50
8.00
The standard overload curves are shown in the following chart. Note that K+E 11" x 17" format of
time/overcurrent curves are available from factory upon request.
4-8
1
2
3
7200
7200
416
833
1250
198
397
596
126
253
380
91
182
273
70
140
210
42
84
127
29
58
87
21
43
64
16
33
50
13
26
39
10
21
32
7.8
15
23
5.8
11
17
4.5
9
13
3.6
7.2
10
3
6
9
2.5
5
7.5
2.1
4.2
6.3
1.8
3.6
5.4
1.6
3.2
4.8
1.4
2.8
4.2
MM2 Motor Manager 2

4.3.2 STANDARD OVERLOAD CURVES

CURVE NUMBER
4
5
6
7200
7200
7682
1666
2916
3750
795
1392
1789
507
887
1141
364
638
820
280
490
630
169
297
381
116
204
262
86
150
193
66
116
150
53
93
119
43
76
98
31
54
69
23
40
52
18
31
40
14
25
32
12
20
26
10
17
22
8.4
14
19
7.2
12
16
6.4
11
14
5.6
9.8
12
4 SETPOINTS

4.3.1 DESCRIPTION

7
8
10243
12804
5000
6250
2386
2982
1521
1902
1093
1367
840
1050
509
636
350
437
258
323
200
250
159
199
131
164
93
116
69
87
54
68
43
54
35
44
30
37
25
31
21
27
19
23
16
20
GE Power Management