Environmental; Type Tests; Production Tests; Approvals - GE T35 Instruction Manual

Transformer management relay ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
OPERATING TEMPERATURES
Cold:
IEC 60028-2-1, 16 h at –40°C
Dry Heat:
IEC 60028-2-2, 16 h at +85°C
Electrical fast transient: ANSI/IEEE C37.90.1
IEC 61000-4-4
IEC 60255-22-4
Oscillatory transient:
ANSI/IEEE C37.90.1
IEC 61000-4-12
Insulation resistance:
IEC 60255-5
Dielectric strength:
IEC 60255-6
ANSI/IEEE C37.90
Electrostatic discharge: EN 61000-4-2
Surge immunity:
EN 61000-4-5
RFI susceptibility:
ANSI/IEEE C37.90.2
IEC 61000-4-3
IEC 60255-22-3
Ontario Hydro C-5047-77
THERMAL
Products go through a 12 h burn-in process at 60°C

APPROVALS

UL Listed for the USA and Canada
Manufactured under an ISO9000 registered system.
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds)
of torque.
GE Multilin
OTHER
Humidity (noncondensing): IEC 60068-2-30, 95%, Variant 1, 6
Altitude:
Installation Category:
Conducted RFI:
Voltage dips/interruptions/variations:
Power frequency magnetic field immunity:
Vibration test (sinusoidal): IEC 60255-21-1
Shock and bump:
Type test report available upon request.
NOTE
CE:
LVD 73/23/EEC:
EMC 81/336/EEC:
CLEANING
Normally, cleaning is not required; but for situations where dust
has accumulated on the faceplate display, a dry cloth can be used.
T35 Transformer Management Relay
2.2 SPECIFICATIONS

2.2.10 ENVIRONMENTAL

days
Up to 2000 m
II

2.2.11 TYPE TESTS

IEC 61000-4-6
IEC 61000-4-11
IEC 60255-11
IEC 61000-4-8
IEC 60255-21-2

2.2.12 PRODUCTION TESTS

2.2.13 APPROVALS
IEC 1010-1
EN 50081-2, EN 50082-2

2.2.14 MAINTENANCE