5 SETTINGS
The nominal three-phase power is:
The three-phase power with 20% overload margin is:
The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
The minimum and maximum power values to be monitored (in pu) are:
minimum power
=
The following settings should be entered:
DCMA OUTPUT H1 SOURCE
: "–1 to 1 mA"
DCMA OUTPUT H1 RANGE
DCMA OUTPUT H1 MIN VAL
DCMA OUTPUT H1 MIN VALL
With the above settings, the output will represent the power with the scale of 1 mA per 20.65 MW. The worst-case error for
this application can be calculated by superimposing the following two sources of error:
±0.5% of the full scale for the analog output module, or
±1% of reading error for the active power at power factor of 0.9
For example at the reading of 20 MW, the worst-case error is 0.01 × 20 MW + 0.207 MW = 0.407 MW.
EXAMPLE 2:
The phase A current (true RMS value) is to be monitored via the H2 current output working with the range from 4 to 20 mA.
The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow-
ing for 50% overload.
The phase current with the 50% overload margin is:
The base unit for current (refer to the FlexElements section in this chapter for additional details) is:
The minimum and maximum power values to be monitored (in pu) are:
minimum current
The following settings should be entered:
DCMA OUTPUT H2 SOURCE
: "4 to 20 mA"
DCMA OUTPUT H2 RANGE
DCMA OUTPUT H2 MIN VAL
DCMA OUTPUT H2 MIN VAL
The worst-case error for this application could be calculated by superimposing the following two sources of error:
±0.5% of the full scale for the analog output module, or
±0.25% of reading or ±0.1% of rated (whichever is greater) for currents between 0.1 and 2.0 of nominal
For example, at the reading of 4.2 kA, the worst-case error is max(0.0025 × 4.2 kA, 0.001 × 5 kA) + 0.504 kA = 0.515 kA.
EXAMPLE 3:
A positive-sequence voltage on a 400 kV system measured via Source 2 is to be monitored by the dcmA H3 output with a
range of 0 to 1 mA. The VT secondary setting is 66.4 V, the VT ratio setting is 6024, and the VT connection setting is
"Delta". The voltage should be monitored in the range from 70% to 110% of nominal.
GE Multilin
×
×
P
3
13.8 kV 0.8 kA
=
×
P
1.2 17.21 MW
=
max
×
×
P
115 V 120
=
BASE
20.65 MW
------------------------------
1.247 pu,
=
16.56 MW
: "SRC 1 P"
: "–1.247 pu"
"1.247 pu"
×
I
1.5 4.2 kA
=
max
I
=
BASE
0 kA
0 pu,
maximum current
----------- -
=
=
5 kA
: "SRC 1 Ia RMS"
: "0.000 pu"
: "1.260 pu"
T35 Transformer Management Relay
×
0.9
17.21 MW
=
20.65 MW
=
1.2 kA
16.56 MW
=
20.65 MW
maximum power
-------------------------- -
=
16.56 MW
±
×
(
– ( )
)
×
0.005
1
1
20.65 MW
6.3 kA
=
5 kA
6.3 kA
1.26 pu
---------------- -
=
=
5 kA
±
×
(
) 6.3 kA
×
0.005
20 4
=
5.8 TRANSDUCER I/O
(EQ 5.33)
(EQ 5.34)
(EQ 5.35)
1.247 pu
(EQ 5.36)
=
±
0.207 MW
=
(EQ 5.37)
(EQ 5.38)
(EQ 5.39)
±
0.504 kA
5-111
5