2.13 TECHNICAL SPECIFICATIONS
Operating Temperatures:
Ambient Storage Temperatures:
Maximum relative humidity
Altitude
Pollution Degree
2
The MIWII system complies with the following standards, which include the standards required by Community Directive 89/
336 for the CE marking, in line with European standards. It also complies with the European directive requirements for low
voltage, and the environmental and operating requirements established in ANSI standards C37.90, IEC 255-5, IEC 255-6
and IEC 68.
STANDARD
ELECTROSTATIC COMPATIBILITY AND INSULATION
IEC 60255-25 / EN 61000-6-4 (2001)
ENV 50204 (1995)
IEC 60255-22-2 / EN 61000-6-2 (2001)
IEC 60255-22-3 / EN 61000-6-2 (2001) /
ENV 50204 (1995)
IEC 60255-22-4
IEC 60255-22-5 / EN 61000-6-2 (2001)
IEC 60255-21-6 / EN 61000-6-2 (2001)
IIEC 60255-11 / EN 61000-6-2 (2001)
IEC 60255-22-1 (1988)
IEC 61000-4-8 (1993) / IEC 61000-4-8
(1993)
IEC 60255-5 (1977)
IEC 60255-5 (1977)
IEC 60255-5 (1977)
2-24
-20º C to +60º C
-40º C to +80º C
95%
2000 m. Max
2
DESCRIPTION
Conducted and Radiated Emission
Radiated Electromagnetic Fields with
Frequency Modulation
Electrostatic Discharge Immunity Test
Radiated RF Fields Immunity Test
Electrical Fast Transient Immunity Test
Surge Immunity Test
Injected RF Signals Immunity Test
Voltage Dips and Interruptions Immunity
Tetst
1 MHz Burst Disturbance Test
50 Hz Magnetic Fields Immunity Test
Measurement of Insulation Resistance
Impulse Voltage Test
Dielectric Test
MIWII Directional Power Protection System
2 PRODUCT DESCRIPTION

2.13.7 ENVIRONMENTAL

2.13.8 TYPE TESTS & CERTIFICATIONS
CLASS
10 V/m, 900 MHz
Level 4 CM (8 kV). Level 3 AM (8 kV)
Level 3 (10 V/m), 80-1000 MHz.
Level 3 (±2 kV except for communications
terminals RS-485 and RS-232 where the
level was ±1 kV) with a perfomance criteria
A.
Level 3 (±2kV CM, ±1kV DM)
Level 3 (10 V/m), 0.15 – 80 MHz.
Duration and Voltage described in the
related report.
Level 3 (±2.5 kV in common mode and ± 1
kV in differential mode) in the I/O terminals
specified in paragraph 4.2 of the
corresponding report.
Level 5 (100 A/m for continuous applications
and 1000 A/m for transient applications) with
a performance criteria A.
In the paragraph relating to insulation
resistance for all groups defined in
paragraph 4 of the report.
In the paragraph relating to impulse voltage
test for ±5 kV applicatios in common mode
and ± 1 kV in differential mode (class III) for
all the groups defined in paragraph 4 of the
correspond report.
In the paragraph relating to dielectric test for
2 kV, 50 Hz applications for all the groups
defined in paragraph 4 of the correspond
report.
GEK-113308