Dnp Communications; Dnp Protocol; Device Profile Document; Binary Inputs - GE T35 Instruction Manual

Transformer management relay ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

APPENDIX E
APPENDIX E DNP COMMUNICATIONSE.1DNP PROTOCOL
The following table provides a 'Device Profile Document' in the standard format defined in the DNP 3.0 Subset Definitions
Document.
Table E–1: DNP V3.00 DEVICE PROFILE (Sheet 1 of 3)
(Also see the IMPLEMENTATION TABLE in the following section)
Vendor Name: General Electric Multilin
Device Name: UR Series Relay
Highest DNP Level Supported:
For Requests:
Level 2
For Responses: Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Binary Counters (Object 20)
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received:
292
Maximum Data Link Re-tries:
None
Ë
Fixed at 2
Ë

Configurable
Ë
Requires Data Link Layer Confirmation:
Ë
Never

Always
Ë
Sometimes
Ë
Configurable
Ë
GE Multilin
Device Function:
Master
Ë
Slave
Ë

Maximum Application Fragment Size (octets):
Transmitted: 240
Received:
Maximum Application Layer Re-tries:
None
Ë

Configurable
Ë
T35 Transformer Management Relay
E.1 DNP PROTOCOL
E.1.1 DEVICE PROFILE DOCUMENT
2048
E
E-1