B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 9 of 29)
ADDR
REGISTER NAME
40B1
DNP Energy Scale Factor
40B2
DNP Other Scale Factor
40B3
DNP Current Default Deadband
40B4
DNP Voltage Default Deadband
40B5
DNP Power Default Deadband
B
40B6
DNP Energy Default Deadband
40B7
DNP Other Default Deadband
40B8
DNP IIN Time Sync Bit Period
40B9
DNP Message Fragment Size
40BA
DNP Client Address 3
40BC
DNP Client Address 4
40BE
DNP Client Address 5
40C0
DNP Communications Reserved (8 items)
40C8
UCA Logical Device Name
40D0
GOOSE Function
40D1
UCA GLOBE.ST.LocRemDS Flexlogic Operand
40D2
UCA Communications Reserved (14 items)
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
40E1
IEC 60870-5-104 Protocol Function
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
40E3
IEC 60870-5-104 Protocol Cyclic Data Trans. Period
40E4
IEC Number of Sources used in M_ME_NC_1 point list
40E5
IEC Current Default Threshold
40E6
IEC Voltage Default Threshold
40E7
IEC Power Default Threshold
40E8
IEC Energy Default Threshold
40E9
IEC Other Default Threshold
40EA
IEC Client Address (5 items)
40FE
IEC Communications Reserved (2 items)
4100
DNP Binary Input Block of 16 Points (58 items)
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
4169
Simple Network Time Protocol (SNTP) Server IP Address
416B
Simple Network Time Protocol (SNTP) UDP Port Number
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
Data Logger (Read/Write Setting)
4180
Data Logger Rate
4181
Data Logger Channel Settings (16 items)
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
Clock (Read/Write Setting)
41A2
SR Date Format
41A4
SR Time Format
41A6
IRIG-B Signal Type
41A7
Clock Events Enable / Disable
Oscillography (Read/Write Setting)
41C0
Oscillography Number of Records
41C1
Oscillography Trigger Mode
41C2
Oscillography Trigger Position
41C3
Oscillography Trigger Source
41C4
Oscillography AC Input Waveforms
41D0
Oscillography Analog Channel X (16 items)
4200
Oscillography Digital Channel X (63 items)
B-16
RANGE
0 to 8
0 to 8
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
1 to 10080
30 to 2048
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
---
0 to 1
0 to 65535
0 to 1
1 to 65535
0 to 1
0 to 65535
1 to 65535
1 to 6
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 4294967295
0 to 1
0 to 58
0 to 1
0 to 4294967295
1 to 65535
0 to 1
0 to 7
---
0 to 235959
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
1 to 64
0 to 1
0 to 100
0 to 65535
0 to 4
0 to 65535
0 to 65535
T35 Transformer Management Relay
APPENDIX B
UNITS
STEP
FORMAT
---
1
F194
---
1
F194
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
min
1
F001
---
1
F001
---
1
F003
---
1
F003
---
1
F003
---
1
F001
---
---
F203
---
1
F102
---
1
F300
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F001
---
1
F197
---
1
F102
---
1
F003
---
1
F001
---
1
F126
---
1
F178
---
---
F600
---
1
F050
---
1
F051
---
1
F052
---
1
F114
---
1
F102
---
1
F001
---
1
F118
0 (Auto. Overwrite)
%
1
F001
---
1
F300
---
1
F183
2 (16 samples/cycle)
---
1
F600
---
1
F300
DEFAULT
2 (1)
2 (1)
30000
30000
30000
30000
30000
1440
240
0
0
0
0
"UCADevice"
1 (Enabled)
0
0
2404
0 (Disabled)
0
60
1
30000
30000
30000
30000
30000
0
0
0 (Not Used)
0 (Disabled)
0
123
0 (No)
1 (1 min)
0
0
0
0
0 (None)
0 (Disabled)
15
50
0
0
0
GE Multilin