5.6 CONTROL ELEMENTS
SELECTOR 1 POWER-UP MODE: This setting specifies behavior of the element on power up of the relay. When set
to "Restore", the last selector position, stored in non-volatile memory, is restored after powering up the relay. When set
to "Synchronize", the selector sets to the current 3-bit control input after powering up the relay. This operation does not
wait for time-out or the acknowledging input. When powering up, the rest position (0, 0, 0) and the out-of-range 3-bit
control words are also ignored, the output is set to Position 0 (no output operand selected), and an alarm is established
(
SELECTOR 1 PWR ALARM
selected) is applied and an alarm is set (
SELECTOR 1 EVENTS: If enabled, the following events are logged:
EVENT NAME
SELECTOR 1 POS Z
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
The following figures illustrate the operation of the Selector Switch. In these diagrams, "T" represents a time-out setting.
STEP-UP
5
3BIT A0
3BIT A1
3BIT A2
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
5-92
). If the position restored from memory is out-of-range, Position 0 (no output operand
SELECTOR 1 PWR ALARM
DESCRIPTION
Selector 1 changed its position to Z.
The selector position pre-selected via the stepping up control input has not been
confirmed before the time out.
The selector position pre-selected via the 3-bit control input has not been confirmed
before the time out.
pre-existing
changed to 4 with
changed to 1 with
position 2
a pushbutton
a 3-bit input
T
T
Figure 5–47: TIME-OUT MODE
T35 Transformer Management Relay
).
changed to 2 with a
changed to 7 with
pushbutton
a 3-bit input
T
T
5 SETTINGS
842737A1.CDR