Relay Activation; Relay Passwords; Flexlogic™ Customization; Commissioning - GE T35 Instruction Manual

Transformer management relay ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

1 GETTING STARTED
The relay is defaulted to the "Not Programmed" state when it leaves the factory. This safeguards against the installation of
a relay whose settings have not been entered. When powered up successfully, the Trouble LED will be on and the In Ser-
vice LED off. The relay in the "Not Programmed" state will block signaling of any output relay. These conditions will remain
until the relay is explicitly put in the "Programmed" state.
Select the menu message
SETTINGS
RELAY SETTINGS:
Not Programmed
To put the relay in the "Programmed" state, press either of the
plate Trouble LED will turn off and the In Service LED will turn on. The settings for the relay can be programmed manually
(refer to Chapter 5) via the faceplate keypad or remotely (refer to the enerVista URPC Setup Help file) via the enerVista
URPC Setup software interface.
It is recommended that passwords be set up for each security level and assigned to specific personnel. There are two user
password security access levels, COMMAND and SETTING:
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol-
lowing operations:
change state of virtual inputs
clear event records
clear oscillography records
operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level
passwords.
NOTE
FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex-
Logic™ section in Chapter 5 for additional details.
Templated tables for charting all the required settings before entering them via the keypad are available from the GE Multi-
lin website at http://www.GEindustrial.com/multilin.
GE Multilin
!
!"
PRODUCT SETUP
INSTALLATION
T35 Transformer Management Relay

1.5.4 RELAY ACTIVATION

!
RELAY SETTINGS
VALUE
keys once and then press

1.5.5 RELAY PASSWORDS

1.5.6 FLEXLOGIC™ CUSTOMIZATION
1.5 USING THE RELAY
. The face-

1.5.7 COMMISSIONING

1-13