Records; User-Programmable Fault Reports; Event Records; Oscillography - GE T35 Instruction Manual

Transformer management relay ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

6.4 RECORDS

6.4RECORDS
PATH: ACTUAL VALUES
# USER-PROGRAMMABLE
# FAULT REPORT
This menu displays the User-Programmable Fault Report actual values. See the User-Programmable Fault Report section
in Chapter 5 for additional information on this feature.
PATH: ACTUAL VALUES

# EVENT RECORDS

#
6
The Event Records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. Refer to the
PATH: ACTUAL VALUES

# OSCILLOGRAPHY

#
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
'cycles per record' value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillogra-
phy section of Chapter 5 for further details.
A trigger can be forced here at any time by setting "Yes" to the
menu for clearing the oscillography records.
CLEAR RECORDS
6-16
!"
!
RECORDS
USER-PROGRAMMABLE FAULT REPORT
NEWEST RECORD
NUMBER: 0
LAST CLEARED DATE:
MESSAGE
2002/8/11 14:23:57
LAST REPORT DATE:
MESSAGE
2002/10/09 08:25:27
!"
!"
RECORDS
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
MESSAGE
POWER ON
EVENT: 2
MESSAGE
POWER OFF
EVENT: 1
MESSAGE
EVENTS CLEARED
"
COMMANDS
CLEAR RECORDS
!"
!"
RECORDS
OSCILLOGRAPHY
FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
MESSAGE
0
AVAILABLE RECORDS:
MESSAGE
0
CYCLES PER RECORD:
MESSAGE
0.0
LAST CLEARED DATE:
MESSAGE
2000/07/14 015:40:16
T35 Transformer Management Relay

6.4.1 USER-PROGRAMMABLE FAULT REPORTS

menu for clearing event records.
Range: No, Yes
command. Refer to the
FORCE TRIGGER?
6 ACTUAL VALUES
6.4.2 EVENT RECORDS
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps
6.4.3 OSCILLOGRAPHY
COMMANDS
GE Multilin
!"

Advertisement

Table of Contents
loading

Table of Contents