5.2 PRODUCT SETUP
!
PATH: SETTINGS
PRODUCT SETUP
# FAST PROD EXCH 1
# CONFIGURATION
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The T35 has one fast exchange (Exchange 1) and
two slow exchanges (Exchanges 2 and 3).
The settings menu for the slow EGD exchanges is shown below:
!
PATH: SETTINGS
PRODUCT SETUP
# SLOW PROD EXCH 1
# CONFIGURATION
5
Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the
fast and slow exchanges are described below:
EXCH 1 DESTINATION: This setting specifies the destination IP address of the produced EGD exchange. This is usu-
ally unicast or broadcast.
EXCH 1 DATA RATE: This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms,
the exchange data will be updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data will be
updated and sent once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a
setting range of 500 to 1000 ms.
EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any
data from the T35 memory map can be configured to be included in an EGD exchange. The settings are the starting
Modbus register address for the data item in decimal format. Refer to Appendix B for the complete Modbus memory
map. Note that the Modbus memory map displays shows addresses in hexadecimal format; as such, it will be neces-
sary to convert these values to decimal format before entering them as values for these setpoints.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (e.g. 32 bit integers and floating point values), only the first
Modbus address is required. The EGD exchange configured with these settings contains the data items up to the first
setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus
addresses and the fourth is 0, the produced EGD exchange will contain three data items.
5-18
!"
COMMUNICATIONS
EXCH 1 FUNCTION:
Disable
EXCH 1 DESTINATION:
MESSAGE
0.0.0.0
EXCH 1 DATA RATE:
MESSAGE
1000 ms
EXCH 1 DATA ITEM 1:
MESSAGE
0
EXCH 1 DATA ITEM 20:
MESSAGE
0
!"
COMMUNICATIONS
EXCH 1 FUNCTION:
Disable
EXCH 1 DESTINATION:
MESSAGE
0.0.0.0
EXCH 1 DATA RATE:
MESSAGE
1000 ms
EXCH 1 DATA ITEM 1:
MESSAGE
0
EXCH 1 DATA ITEM 50:
MESSAGE
0
T35 Transformer Management Relay
!"
!
EGD PROTOCOL
FAST PROD EXCH 1 CONFIGURATION
Range: Disable, Enable
Range: standard IP address
Range: 50 to 1000 ms in steps of 1
Range: 0 to 65535 in steps of 1
(Modbus register address range)
Range: 0 to 65535 in steps of 1
(Modbus register address range)
!"
!
EGD PROTOCOL
SLOW PROD EXCH 1(2) CONFIGURATION
Range: Disable, Enable
Range: standard IP address
Range: 500 to 1000 ms in steps of 1
Range: 0 to 65535 in steps of 1
(Modbus register address range in decimal)
Range: 0 to 65535 in steps of 1
(Modbus register address range in decimal)
5 SETTINGS