CHAPTER 1: INTRODUCTION

1.5.10 Physical specifications

1.5.11 Environmental specifications

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
TYPE TESTS
Relative Humidity Cyclic: .................................IEC 60068-2-30: 55°C at 95% RH
Hot: ............................................................................IEC 60068-2-2 (Hot Start) 16 hours /+85°C
Cold: ..........................................................................IEC 60068-2-1 (Cold Start) 16 hours / -40°C
Dielectric Strength:.............................................IEC 60255-5: 2300 VAC
Insulation Resistance:.......................................IEC 60255-5: >100 MΩ / 500 VDC / 10 s
Impulse Voltage:..................................................IEC 60255-5: 5 kV / 0.5 J
Sinusoidal Vibration:..........................................IEC 60255-21-1: 2 g, Class 2
Shock and Bump:................................................IEC 60255-21-2: 10 g / 20 g / 30 g, Class 2
Seismic:....................................................................IEC 60255-21-3: 2 g
Damped Oscillatory Burst:..............................IEC 60255-22-1: 1 MHz 2.5 kV / 1 kV
Electrostatic Discharge Immunity - Air
and Direct:.........................................................IEC 60255-22-2: 8 kV / 6 kV
Radiated RF Immunity:.....................................IEC 60255-22-3: 10 V/m (80 MHz to 1 GHz / 1.4 to 2.7 GHz)
Electrical Fast Transient / Burst
Immunity: ..........................................................IEC 60255-22-4: ±4 kV
Surge Immunity: ..................................................IEC 60255-22-5: ±2 kV / 1 kV
Conducted RF Immunity:.................................IEC 60255-22-6: 150 kHz to 80 MHz 10 V/m
Radiated RF Emission: ......................................IEC 60255-25: EN55022, Class A
Conducted RF Emission: ..................................IEC 60255-25: EN55022, Class A
Ingress of Solid Objects and Water:...........IEC 60529: IP40 (front), IP10 (back)
Power Frequency Magnetic Field
Immunity: ..........................................................IEC 61000-4-8: 30 A/m, 1000 A/m, Class 5
Pulse Magnetic Field Immunity: ...................IEC 61000-4-9: 1000 A/m
Voltage Dip; Voltage Interruption:...............IEC 61000-4-11: 0%, 40%, 100%
Fast Transient SWC:...........................................IEEE C37.90.1: ±4 kV
Oscillatory Transient SWC: .............................IEEE C37.90.1: ±2.5 kV
Electrostatic Discharge - Air and Direct: ..IEEE C37.90.3: ±8 kV / ±6 kV
DIMENSIONS
Size: ...........................................................................Refer to section 2.1.1
Weight:.....................................................................4.1 kg [9.0 lb]
OPERATING ENVIRONMENT
Ambient operating temperature: ................–40°C to +60°C [-40°F to +140°F]
Ambient storage / shipping
temperature:....................................................–40°C to +85°C [-40°F to +185°F]
Humidity:.................................................................up to 90% non-condensing
Pollution degree: .................................................2
Installation category: ........................................I
Overvoltage category:......................................III