GE T35 Instruction Manual page 105

Transformer management relay ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

5 SETTINGS
The control pushbuttons are typically not used for critical operations. As such, they are not protected by the control pass-
word. However, by supervising their output operands, the user can dynamically enable or disable the control pushbuttons
for security reasons.
Each control pushbutton asserts its own FlexLogic™ operand,
configured appropriately to perform the desired function. The operand remains asserted as long as the pushbutton is
pressed and resets when the pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton
manipulation will be recognized by various features that may use control pushbuttons as inputs.
An event is logged in the Event Record (as per user setting) when a control pushbutton is pressed; no event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key
must be released before the next one can be pressed.
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL
Enabled=1
SYSTEM SETUP/
BREAKERS/BREAKER 2/
BREAKER 2 PUSHBUTTON
CONTROL
Enabled=1
GE Multilin
STATUS
EVENT CAUSE
IN SERVICE
VOLTAGE
TROUBLE
CURRENT
RESET
TEST MODE
FREQUENCY
TRIP
OTHER
USER 1
ALARM
PHASE A
PICKUP
PHASE B
USER 2
PHASE C
NEUTRAL/GROUND
USER 3
USER 4
USER 5
USER 6
USER 7
Figure 5–3: CONTROL PUSHBUTTONS
:
AND
RUN
OFF
ON
:
Figure 5–4: CONTROL PUSHBUTTON LOGIC
T35 Transformer Management Relay
THREE
STANDARD
CONTROL
PUSHBUTTONS
FOUR EXTRA
OPTIONAL
CONTROL
PUSHBUTTONS
842733A2.CDR
CONTROL PUSHBTN 1(7) ON
TIMER
FLEXLOGIC OPERAND
0
CONTROL PUSHBTN 1 ON
100 msec
5.2 PRODUCT SETUP
. These operands should be
842010A2.CDR
5-27
5