6 ACTUAL VALUES
b) STATISTICS
!
PATH: ACTUAL VALUES
STATUS
# REMOTE DEVICE
1
#
MESSAGE
Statistical data (2 types) for up to 16 programmed Remote Devices is shown here.
The StNum number is obtained from the indicated Remote Device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated Remote Device and is incremented
whenever a GOOSE message is sent. This number will rollover to zero when a count of 4,294,967,295 is incremented.
!
PATH: ACTUAL VALUES
STATUS

# SELECTOR SWITCHES

#
MESSAGE
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
!
PATH: ACTUAL VALUES
STATUS

# FLEX STATES

#
MESSAGE
There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit.
!
PATH: ACTUAL VALUES
STATUS

# ETHERNET

#
MESSAGE
GE Multilin
!"
REMOTE DEVICES STATISTICS
REMOTE DEVICE
1
StNum:
REMOTE DEVICE
1
SqNum:
!"
SELECTOR SWITCHES
SELECTOR SWITCH 1
POSITION: 0/7
SELECTOR SWITCH 2
POSITION: 0/7
!"
FLEX STATES
PARAM
1: Off
Off
PARAM 256: Off
Off
!"
ETHERNET
ETHERNET PRI LINK
STATUS: OK
ETHERNET SEC LINK
STATUS: OK
T35 Transformer Management Relay
!
REMOTE DEVICE 1(16)
0
0
6.2.7 SELECTOR SWITCHES
Range: Current Position / 7
Range: Current Position / 7
Range: Off, On
Range: Off, On
Range: Fail, OK
Range: Fail, OK
6.2 STATUS
6.2.8 FLEX STATES
6
6.2.9 ETHERNET