Advertisement

5.2 PRODUCT SETUP
!
PATH: SETTINGS
PRODUCT SETUP
# USER-PROGRAMMABLE
# SELF TESTS
5
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the Minor Alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, display target
messages. Moreover, they will not trigger the
minor alarms continue to function along with other major and minor alarms. Refer to the Relay Self-Tests section in Chapter
7 for additional information on major and minor self-test alarms.
!
PATH: SETTINGS
PRODUCT SETUP
# CONTROL
# PUSHBUTTON 1
The three standard pushbuttons located on the top left panel of the faceplate are user-programmable and can be used for
various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-pro-
grammable displays, etc. The location of the control pushbuttons in the following figure.
An additonal four control pushbuttons are included when the T35 is ordered with twelve user programmable pushbuttons.
5-26
!"

USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
MESSAGE
FUNCTION: Enabled
REMOTE DEVICE OFF
MESSAGE
FUNCTION: Enabled
PRI. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
BATTERY FAIL
MESSAGE
FUNCTION: Enabled
SNTP FAIL
MESSAGE
FUNCTION: Enabled
IRIG-B FAIL
MESSAGE
FUNCTION: Enabled
ANY MINOR ALARM
!"

CONTROL PUSHBUTTONS

CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
MESSAGE
EVENTS: Disabled
T35 Transformer Management Relay
5.2.11 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled.
Valid for units equipped with Direct I/O Module.
Range: Disabled, Enabled.
Valid for units equipped with Direct I/O Module.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type D.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
or
messages. When in the "Enabled" mode,
ANY SELF-TEST
5.2.12 CONTROL PUSHBUTTONS
!
CONTROL PUSHBUTTON 1(7)
Range: Disabled, Enabled
Range: Disabled, Enabled
5 SETTINGS
GE Multilin