5 SETTINGS
d) EXAMPLE
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at 8 times pickup with an operating time of 30 ms. At approximately 4 times pickup, the curve operating time is
equal to the MRT and from then onwards the operating time remains at 200 ms (see below).
Figure 5–18: COMPOSITE RECLOSER CURVE WITH HCT DISABLED
With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding 8 times pickup.
Figure 5–19: COMPOSITE RECLOSER CURVE WITH HCT ENABLED
Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If this
is attempted, the enerVista URPC Setup software generates an error message and discards the proposed
changes.
NOTE
e) STANDARD RECLOSER CURVES
The standard Recloser curves available for the T35 are displayed in the following graphs.
GE Multilin
T35 Transformer Management Relay
5.3 SYSTEM SETUP
842719A1.CDR
5
842720A1.CDR
5-55