Physical; Environmental - GE Multilin 350 Series Instruction Manual

Feeder protection system
Hide thumbs Also See for Multilin 350 Series:
Table of Contents

Advertisement

CHAPTER 1: INTRODUCTION

Physical

Environmental

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
Damped Magnetic Immunity
Voltage Dip & interruption
Damped Oscillatory
Conducted RF Immunity 0-150khz IEC61000-4-16
Voltage Ripple
Ingress Protection
Environmental (Cold)
Environmental (Dry heat)
Relative Humidity Cyclic
EFT
Damped Oscillatrory
RF Immunity
ESD
Safety
DIMENSIONS
Size: ...........................................................................Refer to Chapter 2
Weight:.....................................................................4.1 kg [9.0 lb]
Ambient temperatures:
Storage/Shipping:
Operating:
Humidity:
Altitude:
Pollution Degree:
Overvoltage Category:
Ingress Protection:
IEC61000-4-10
IEC61000-4-11
IEC61000-4-12
IEC61000-4-17
IEC60529
IEC60068-2-1
IEC60068-2-2
IEC60068-2-30
IEEE/ANSI C37.90.1
IEEE/ANSI C37.90.1
IEEE/ANSIC37.90.2
IEEE/ANSIC37.90.3
UL508
UL C22.2-14
UL1053
- 40C to 85C
-40C to 60C
Operating up to 95% (non condensing) @ 55C (As per
IEC60068-2-30 Variant 2, 6days)
2000m (max)
II
III
IP40 Front , IP10 back
SPECIFICATIONS
Level 4
0, 40, 70, 80% dips, 250/
300 cycle interrupts
2.5KV CM, 1KV DM
Level 4
15% ripple
IP40 front , IP10 Back
-40C 16 hrs
85C 16hrs
6day variant 2
4KV, 2.5Khz
2.5KV,1Mhz
20V/m 80-1Ghz
8KV CD/ 15KV AD
e83849 NKCR
e83849 NKCR7
e83849 NKCR
1–15