1 GETTING STARTED
Enter the relay slave address and COM port values (from the
!"
menu) in the "Slave Address" and "COM Port" fields.
SERIAL PORTS
Enter the physical communications parameters (baud rate and parity settings) in their respective fields.
8.
Click the Read Order Code button to connect to the T35 device and upload the order code. If an communications error
occurs, ensure that the enerVista URPC Setup serial communications values entered in the previous step correspond
to the relay setting values.
9.
Click "OK" when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main enerVista URPC Setup window.
The Site Device has now been configured for RS232 communications. Proceed to Section c) Connecting to the Relay
below to begin communications.
c) CONNECTING TO THE RELAY
1.
Open the Display Properties window through the Site List tree as shown below:
2.
The Display Properties window will open with a status indicator on the lower left of the enerVista URPC Setup window.
3.
If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly setup for communications (steps A and B earlier).
If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4.
The Display Properties settings can now be edited, printed, or changed according to user specifications.
GE Multilin
Expand the Site List by double-clicking
or by selecting the [+] box
Communications Status Indicator
Green LED = OK, Red LED = No Communications
UR icon = report open
T35 Transformer Management Relay
1.3 ENERVISTA URPC SETUP SOFTWARE
!