GE T35 Instruction Manual page 155

Transformer management relay ur series
Hide thumbs Also See for T35:
Table of Contents

Advertisement

5 SETTINGS
b) PERCENT DIFFERENTIAL
!"
PATH: SETTINGS
GROUPED ELEMENTS
# PERCENT
# DIFFERENTIAL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The calculation of differential (I
by the following block diagram, where "Σ" has as its output the vector sum of inputs, and "max" has as its output the input of
maximum magnitude; these calculations are performed for each phase.
GE Multilin
!
SETTING GROUP 1(6)
PERCENT DIFFERENTIAL
FUNCTION: Disabled
PERCENT DIFFERENTIAL
PICKUP:
0.100 pu
PERCENT DIFFERENTIAL
SLOPE 1:
25%
PERCENT DIFFERENTIAL
BREAK 1: 2.000 pu
PERCENT DIFFERENTIAL
BREAK 2: 8.000 pu
PERCENT DIFFERENTIAL
SLOPE 2: 100%
INRUSH INHIBIT
FUNCTION: Adapt. 2nd
INRUSH INHIBIT
MODE: Per phase
INRUSH INHIBIT
LEVEL: 20.0% fo
OVEREXCITN INHIBIT
FUNCTION: Disabled
OVEREXCITN INHIBIT
LEVEL: 10.0% fo
PERCENT DIFF BLOCK:
Off
PERCENT DIFFERENTIAL
TARGET: Self-reset
PERCENT DIFFERENTIAL
EVENTS: Disabled
) and restraint (I
) currents for the purposes of the percent differential element is described
d
r
T35 Transformer Management Relay
5.5 GROUPED ELEMENTS
!
!
TRANSFORMER
PERCENT DIFFERENTIAL
Range: Disabled, Enabled
Range: 0.050 to 1.000 pu in steps of 0.001
Range: 15 to 100% in steps of 1
Range: 1.000 to 2.000 pu in steps of 0.001
Range: 2.000 to 30.000 pu in steps of 0.001
Range: 50 to 100% in steps of 1
Range: Disabled, Adapt. 2nd, Trad. 2nd
Range: Per phase, 2-out-of-3, Average
Range: 1.0 to 40.0% of f
Range: Disabled, 5th
Range: 1.0 to 40.0% of f
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
in steps of 0.1
0
in steps of 0.1
0
5-77
5