Advertisement

5.7 INPUTS/OUTPUTS
b) USERST BIT PAIRS
!"
PATH: SETTINGS
INPUTS/OUTPUTS
# REMOTE OUTPUTS
# UserSt- 1 BIT PAIR
Remote Outputs 1 to 32 originate as GOOSE messages to be transmitted to remote devices. Each digital point in the mes-
sage must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GOOSE messages when there has been no change of state of
any selected digital point. This setting is located in the
tings menu.
For more information on GOOSE specifications, see the Remote I/O Overview in the Remote Devices sec-
tion.
NOTE
!"
PATH: SETTINGS
INPUTS/OUTPUTS
5

# RESETTING

#
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic™ latches) to the reset
state. The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel,
or any programmed operand.
When the RESET command is received by the relay, two FlexLogic™ operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the
FlexLogic™ operand. Each individual source of a RESET command also creates its individual operand
RESET OP
RESET OP (PUSHBUTTON)
shown above selects the operand that will create the
a) DIRECT INPUTS
!"
PATH: SETTINGS
INPUTS/OUTPUTS
# DIRECT INPUT
#
These settings specify how the Direct Input information is processed. The
this Direct Input. The specified Direct Input is driven by the device identified here.
5-104
!"
REMOTE OUTPUTS UserSt BIT PAIRS
UserSt- 1 OPERAND:
Off
UserSt- 1 EVENTS:
MESSAGE
Disabled
DEFAULT GOOSE UPDATE
TIME: 60 s
!"
RESETTING
RESET OPERAND:
Off
,
or
RESET OP (COMMS)
RESET OP (OPERAND)
!"
DIRECT INPUTS
1
DIRECT INPUT
DEVICE ID: 1
DIRECT INPUT
MESSAGE
BIT NUMBER:
DIRECT INPUT
MESSAGE
DEFAULT STATE: Off
DIRECT INPUT
MESSAGE
EVENTS: Disabled
T35 Transformer Management Relay
!
REMOTE OUTPUTS UserSt- 1(32) BIT PAIR
Range: FlexLogic™ operand
Range: Disabled, Enabled
!"
PRODUCT SETUP
COMMUNICATIONS
Range: 1 to 60 s in steps of 1
Range: FlexLogic™ operand
to identify the source of the command. The setting
operand.
RESET OP (OPERAND)
!
DIRECT INPUT 1(32)
Range: 1 to 16
1
Range: 1 to 32
1
1
Range: On, Off, Latest/On, Latest/Off
1
Range: Enabled, Disabled
1
DIRECT INPUT DEVICE ID
5 SETTINGS
!"
UCA/MMS PROTOCOL
5.7.9 RESETTING

5.7.10 DIRECT INPUTS/OUTPUTS

represents the source of