11.6 Input Terminal Function

It can be assigned the function No. in the following table to parameter f104, f108, f110 to f118, f151 to
f156, a973 to a976.
 Table of input terminal functions 1
Function
Code
No.
0,1
-
2
F
3
FN
4
R
5
RN
6
ST
7
STN
8
RES
9
RESN
10
SS1
11
SS1N
12
SS2
13
SS2N
14
SS3
15
SS3N
16
SS4
17
SS4N
18
JOG
19
JOGN
20
EXT
21
EXTN
22
DB
23
DBN
24
AD2
25
AD2N
26
AD3
27
AD3N
28
VF2
11
29
VF2N
32
OCS2
33
OCS2N
36
PID
37
PIDN
46
OH2
47
OH2N
48
SCLC
49
SCLCN
50
HD
51
HDN
*2: These functions are cannot be assigned to Always active function selection 1 to 3 (f104, f108, f110).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Function
No function
Forward run command
Inversion of forward run command
Reverse run command
Inversion of reverse run command
Standby
Inversion of standby
Reset command 1 *2
Inversion of reset command 1 *2
Preset-speed command 1
Inversion of preset-speed command 1
Preset-speed command 2
Inversion of preset-speed command 2
Preset-speed command 3
Inversion of preset-speed command 3
Preset-speed command 4
Inversion of preset-speed command 4
Jog run mode
Inversion of jog run mode
Emergency stop by external signal
Inversion of emergency stop by external signal
DC braking command
Inversion of DC braking command
2nd acceleration/deceleration
Inversion of 2nd acceleration/deceleration
3rd acceleration/deceleration
Inversion of 3rd acceleration/deceleration
2nd V/F control mode switching
Inversion of 2nd V/F control mode switching
2nd stall prevention level
Inversion of 2nd stall prevention level
PID control prohibition
Inversion of PID control prohibition
External thermal error input
Inversion of external thermal error input
Forced local from communication
Inversion of forced local from communication
Operation hold (hold of 3-wire operation)
Inversion of operation hold (hold of 3-wire
operation)
Action
Disabled
ON: Forward run, OFF: Deceleration stop
Inversion of F
ON: Reverse run, OFF: Deceleration stop
Inversion of R
ON: Ready for operation
OFF: Coast stop (gate OFF)
Inversion of ST
ON: Acceptance of reset command, ON → OFF: Trip reset
Inversion of RES
Selection of 15-speed SS1 to SS4 (SS1N to SS4N) (4 bits)
ON: Jogging mode, OFF: Jog run canceled
Inversion of JOG
ON:  trip stop, OFF: After stopped by f603, e trip
Inversion of EXT
ON: DC braking, OFF: Brake canceled
Inversion of DB
ON: Acceleration/deceleration 2
OFF: Acceleration/deceleration 1
Inversion of AD2
ON: Acceleration/deceleration 3
OFF: Acceleration/deceleration 1 or 2
Inversion of AD3
ON: 2nd V/F control mode
(V/F fixed,  , , ,  (thr when
f632=2 or 3))
OFF: 1st V/F control mode
( setting, , , , )
Inversion of VF2
ON: Enabled at the value of ,  and 
OFF: Enabled at the value of ,  and 
Inversion of OCS2
ON: PID control prohibited, OFF: PID control enabled
Inversion of PID
ON: oh2 trip stop, OFF: Disabled
Inversion of OH2
Enabled during communication
ON: Local (Setting of , )
OFF: Communication
Inversion of SCLC
ON: F (forward run), R: (reverse run) held, 3-wire operation
OFF: Deceleration stop
Inversion of HD
K-30
E6581611
Reference
-
3.2.1
7.2.1
3.2.1
5.9
6.7.1
6.34.8
13.2
5.7
7.2.1
5.7
6.14
6.29.4
6.12.1
6.8.1
6.27.2
6.8.1
6.8.1
6.29.2
6.24
7.2.1
6.2.1
6.38
7.2.1