Toshiba VF-S15 Instruction Manual page 130

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

Steps in setting are as follows
(In this example, the V/F control mode selection parameter  is set to  (Vector control).
[Setting V/F control mode selection to 3 (sensorless vector control)]
Operation panel
6
Caution:
When the V/F control mode selection  is set to : Automatic torque boost control, : Vector control,
: Energy-saving, : Dynamic energy-saving, or : PM motor control, be sure to set the following
parameters according to the motor's name plate.
Set the other motor constants as necessary
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
LED display
action
.
MODE


 

: Base frequency 1 (rated frequency)

: Base frequency voltage 1 (rated voltage) 

: Motor rated capacity 

: Motor rated current

: Motor rated speed
Operation
Displays the output frequency. (Perform during operation stopped.)
(When standard monitor display selection  is set to 
[output frequency])
The first basic parameter "" (history function) is displayed.
Rotate the setting dial to the right, and change the parameter to 
(V/F control mode selection).
Set values are displayed by pressing the center of the setting dial.
Rotate the setting dial to the right, and change the parameter to 
(vector control).
Press the center of the setting dial to save the changed set value.
 and the set value "" are displayed alternately.
F-18
E6581611