6.33.3 Calibration of analog output
f681 : Analog output signal selection
f684 : Analog output filter
f691 : Inclination characteristic of analog output
f692 : Analog output bias
 Function
* Optional frequency meter: When using QS60T, set f681 = 0 (meter option (0 to 1mA) output).
[Parameter setting]
f681  Analog output signal selection
f684  Analog output filter
6
f691
f692
Note 1: In case of 0 to 20mAdc (4 to 20mAdc) output, or 0 to 10Vdc output, set f681 to 1 or 2 .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Output signal from the FM terminal can be switched between 0 to 1mAdc output, 0 to 20mAdc output,
and 0 to 10Vdc output with the f681 setting. The standard setting is 0 to 1mAdc output.
Title
Function
Inclination characteristic of analog
output
Analog output bias
In case of 4 to 20mAdc output, f692 needs adjustment.
Adjustment range
0: Meter option (0 to 1mA)
1: Current (0 to 20mA) output
2: Voltage (0 to 10V) output
2-1000 (ms)
0: Negative inclination (downward slope)
1: Positive inclination (upward slope)
-1.0 - +100.0 (%)
F-122
E6581611
Default setting
0
2
1
0.0