Toshiba VF-S15 Instruction Manual page 98

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

[Using a VF motor (motor for use with inverter)]
 Setting of electronic thermal protection characteristics selection 
 Setting of motor electronic thermal protection level 1  (Same as f173)
2) Motor 150%-overload detection time f607
Parameter f607 is used to set the time elapsed before the motor trips under a load of 150% (overload trip
2) within a range of 10 to 2400 seconds.
3) Inverter overload detection method f631
As this function is set to protect the inverter unit, this function cannot be turned off by parameter setting.
The inverter overload detection method can be selected using parameter f631 (Inverter overload
detection method).
[Parameter setting]
Title
f631
If the inverter overload trip function (ol1) is activated frequently, this can be improved by adjusting the stall
operation level f601 downward or increasing the acceleration time acc or deceleration time dec.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Setting value
Overload protection
valid
valid
invalid
invalid
VF motors (motors designed for use with inverters) can be used in frequency ranges lower than those
for standard motors, but their cooling efficiency decreases at frequencies below 6Hz.
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor
is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1  so
that it fits the motor's rated current.
*
If the indications are in percentages (%), then 100% equals the inverter's rated output current (A).
Output current reduction factor [%]/[A]
×1.0
×0.6
0
6Hz
Note) The start level for motor overload reduction is fixed at 6 Hz.
Function
Inverter overload detection method
Overload stall
invalid
valid
invalid
valid
Output frequency (Hz)
Adjustment range
0: 150%-60s (120%-60s)
1: Temperature estimation
E-11
E6581611
5
Default setting
0

Hide quick links:

Advertisement

Table of Contents
loading