Toshiba VF-S15 Instruction Manual page 55

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

Terminal
Input /
symbol
output
FM
Output
Output
P24
Input
+24
Output
+SU
Input
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Function
Multifunction programmable analog
output. Default setting: output frequency.
The function can be changed to meter
option (0-1mA), 0-10Vdc voltage, or 0-
20mAdc (4-20mA) current output by
parameter  setting.
Resolution Max. 1/1000.
24Vdc power output
This terminal can be used as a common
terminal when an external power supply
is used by changing SW1 to PLC side.
24Vdc power output
DC power input terminal for operating the
control circuit. Connect a control power
backup device (option or 24Vdc power
supply) between +SU and CC.
Electrical
specifications
1mAdc full-scale
ammeter or
QS60T(option)
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
FM
600Ω or less
0-10V DC volt
meter
Permissible load
resistance:
1kΩ or more
24Vdc-100mA
Note 2)
P24
-
+24
24Vdc-100mA
Note 2)
Voltage:
+SU
24Vdc±10%
Current: 1A or
more
B-9
E6581611
Inverter internal circuits
121
+
+24V
+24V
Voltage
Current
+
68
EXT
+24V
Current
limiter
SW1
+24V
1
2