5.4
Upper limit and lower limit frequencies
: Upper limit frequency
Function
Programs the lower limit frequency that determines the lower limit of the output frequency and the upper
limit frequency that determines the upper limit of that frequency.
5
[Parameter setting]
Title
* 1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Note1) Do not set a value 10 times larger than (base frequency 1) and (base frequency 2) for .
If a large number is set, the output frequency can only be output at 10 times of minimum value and
and a-05 alarm is displayed.
Note2) Output frequency lower than parameter f240 (Starting frequency) is not output. Parameter f240
setting is needed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Upper limit
Command frequency (Hz)
0
Frequency setting signal
* Frequencies that go
higher than will not
be output.
Function
Upper limit frequency
Lower limit frequency
: Lower limit frequency
Command frequency (Hz)
frequency
100%
Adjustment range
0.5 - (Hz)
0.0 - (Hz)
E-6
E6581611
Lower limit
frequency
0
100%
Frequency setting signal
* Command frequency
cannot be set lower than
.
Default setting
1