6.4
Manual torque boost - increasing torque boost at low
speeds
vb : Torque boost value 1
Function
If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this
parameter.
6
[Parameter setting]
Title
● Valid when is set to 0 (V/F constant), 1 (Variable torque), or 7 (V/F 5-point setting).
Note 1: The optimum value is programmed for each inverter capacity by default setting. Be careful not to increase
the torque boost rate too much because it could cause an overcurrent trip at startup.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Base frequency voltage
Function
Torque boost value 1
Base frequency
Adjustment range
0.0 - 30.0 (%)
F-24
E6581611
Output frequency (Hz)
Default setting
According to model
(Refer to section 11.4)