6.29.15 Parts replacement alarms
f634 : Annual average ambient temperature (Parts replacement alarms)
 Function
[Parameter setting]
f634
● Display of part replacement alarm information
The time of replacement can be confirmed with the part replacement alarm information in the Status
monitor mode. (Refer to chapter 8)
An example of display:
6
● Output of part replacement alarm signal
The parts replacement alarm is assigned to the output terminal.
Setup example) When the parts replacement alarm is assigned to the OUT terminal
f131 
Setting value 129 is reverse signal.
Note 1: Using f634 , enter the annual average temperature around the inverter. Be careful not to enter the
Note 2: Set f634 at the time of installation of the inverter, and do not change its setting after the start of
● The cumulative power on time, cumulative fan operation time and cumulative operation time until present
time can be checked by setting status monitor mode. (Refer to chapter 8)
● The monitor value of cumulative fan operation time and cumulative operation time are reset to 0(zero) by
parameter typ (Refer to section 4.3.2) .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Calculate the remaining service life of the cooling fan, main circuit capacitor and on-block capacitor
based on the cumulative power on time, cumulative operation time, cumulative fan operation time,
the output current (inverter load factor) and the setting of f634 . An alarm will be monitor displayed
and sent out through output terminals when each component is approaching the time of replacement.
Title
Function
Annual average ambient temperature
(parts replacement alarms)

Title
Function
Output terminal selection 2A
(OUT)
annual highest temperature .
use. Changing the setting may cause parts replacement alarm calculation error.
Adjustment range
1: -10 to +10  C
2: 11-20  C
3: 21-30  C
4: 31-40  C
5: 41-50  C
6: 51-60  C
Adjustment range
0-255
F-112
E6581611
Default setting
3
Setting
128: LTA (Parts replacement
alarm)