Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kilo Amperes,___Y___Volts
maximum, when protected by___Z1___with a maximum rating of___Z2___.
(1) Input withstand rating is that for which the product has been designed thermally. Installation on a supply greater than
this level will require additional inductance to satisfy this level.
(2) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any
additional local codes. This is dependant on the type of installation.
In case of using VF-S15 with a higher AIC capability up to 100kA(*1), install the minimum input inductance or
more listed in the following table. The Short Circuit Current Ratings (SCCR) become 100kA(*1) by installing VF-
S15 with the circuit breakers(GV3P) or the fuses listed in the following table.
 AIC 100kA,
Inverter model
VFS15-2004PM-W
VFS15-2007PM-W
VFS15-2015PM-W
VFS15-2022PM-W
VFS15-2037PM-W
VFS15-2055PM-W
VFS15-2075PM-W
VFS15-2110PM-W
9
VFS15-2150PM-W
VFS15S-2002PL-W
VFS15S-2004PL-W
VFS15S-2007PL-W
VFS15S-2015PL-W
VFS15S-2022PL-W
VFS15-4004PL-W
VFS15-4007PL-W
VFS15-4015PL-W
VFS15-4022PL-W
VFS15-4037PL-W
VFS15-4055PL-W
VFS15-4075PL-W
VFS15-4110PL-W
VFS15-4150PL-W
(*1) In case VFS15-4150PL-W with the circuit breaker, the Short Circuit Current Ratings (SCCR) is 65kA, not 100kA.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Branch circuit protection
Minimum
Branch circuit protection
input
With Fuses
Inductance
(Bussman
/Ferraz)
(mH)
0.05
Class J
0.05
Class J
0.05
Class J
0.05
Class J
0.05
Class J
0.02
Class J
0.02
Class J
0.02
Class J
0.02
Class J
0.28
Class J
0.28
Class J
0.28
Class J
0.28
Class J
0.28
Class J
0.10
Class J
0.10
Class J
0.10
Class J
0.10
Class J
0.10
Class J
0.03
Class J
0.03
Class J
0.03
Class J
0.03
Class J
and Wire sizes
Fuse
With circuit
Breaker
Rating
breakers
Setting
(A)
(Schneider)
(A)
10
GV3P13
9
15
GV3P13
9
25
GV3P13
10
25
GV3P18
18
45
GV3P25
25
60
GV3P40
40
70
GV3P50
50
100
GV3P65
65
110
10
GV3P13
9
15
GV3P13
9
25
GV3P13
13
40
GV3P25
25
45
GV3P32
32
6
GV3P13
9
6
GV3P13
9
15
GV3P13
9
15
GV3P13
10
25
GV3P13
13
40
GV3P18
18
40
GV3P25
25
60
GV3P32
32
70
GV3P40 (*1)
40
I-8
E6581611
Cable
sizes of
Earth Cable
power
circuit
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 12
AWG 14
AWG 10
AWG 10
AWG 8
AWG 10
AWG 6
AWG 10
AWG 6*2
AWG 8
AWG 6*2
AWG 8
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 10
AWG 12
AWG 10
AWG 10
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 14
AWG 12
AWG 14
AWG 10
AWG 10
AWG 8
AWG 10
AWG 8
AWG 10
AWG 6
AWG 10