6.19.7 Reverse-run prohibition
f311 : Reverse-run prohibition
[Parameter setting]

6.20 Drooping control

f320 : Droop gain
f323 : Droop insensitive torque band
f324 : Droop output filter
 Function
[Parameter setting]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
 Function
This function prevents the motor from running in the forward or reverse direction when it receives the
wrong operation signal.
Title
Function
f311
Reverse-run prohibition
Drooping control has the function to prevent loads from concentrating at a specific motor because of
a load imbalance when multiple inverters are used to operate one machine.
These parameters are used to allow the motor to "slip" according to the load torque current. The
insensitive torque band and the gain can be adjusted using these parameters.
Title
Function
f320
Droop gain
f323
Droop insensitive torque band
f324 Droop output filter
Adjustment range
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
Adjustment range
0.0-100.0 (%)
0-100 (%)
0.1-200.0
F-73
E6581611
Default setting
0
6
Default setting
0.0
10
100.0