Toshiba VF-S15 Instruction Manual page 240

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

 When f707 is not 0.00, and f708 is not 0
The value displayed on the panel also can also be changed in steps.
Output frequency displayed in standard monitor mode = Internal output frequency ×
[Parameter setting]
f707
f708  Free step 2 (panel display)
 Operation example 1
f707 = 0.00 (disabled)
By rotating the setting dial 1 step, the panel frequency command value changes only 0.1 Hz.
When f707 = 10.00 (Hz) is set
Rotating the setting dial 1 step changes the panel frequency command value in 10.00 Hz increments, from
0.00 up to 60.00 (Hz).
 Operation example 2
When f707 =1.00 (Hz), and f708 =1:
6
By rotating the setting dial 1 step, the frequency setting fc changes in steps of 1Hz: 0  1  2  ...  60
(Hz) and also the value displayed on the operation panel changes in steps of 1. Use these settings to hide
decimal fractions and also the value displayed on the operation panel changes in steps of 1. Use these
settings to hide decimal fractions.
6.34.5 Select the initial display of the panel
f710 : Initial panel display selection
f720 : Initial extension panel display selection
 Function
 Changing the display format while power is ON
When the power is ON, the standard monitor mode displays the output frequency (default setting) such as
" 0.0 " or " off ". This format can be changed to any other monitor display format by setting f710 .
However, the initial letter including t or c will not be displayed. When the power is ON, set the display of the
extension panel at f720 .
● Different contents can be displayed on the operation panel of main unit and the extension panel (option).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Title
Function
Free step 1 (1-step rotation of setting
dial)
This parameter specifies display format of the standard monitor mode when power is ON. Different
contents can be displayed on the operation panel of main unit and the extension panel (option).
Adjustment range
0.00: Automatic
0.01- fh (Hz)
0: Automatic
1-255
F-128
E6581611


Default setting
0.00
0