Toshiba VF-S15 Instruction Manual page 25

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

1.3.3
1) Power circuit terminal
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Power circuit and control circuit terminal blocks
In case of the lug connector, cover the lug connector with insulated tube, or use the insulated lug
connector.
(Recommended Lug connectors and Insulated Tubes)
Wire Size
Screw Size
2
(mm
)
M3.5 screw
1.5-2.5
1.5-2.5
M4 screw
3.5-5.5
1.5-2.5
3.5-6.0
M5 screw
8.0-10
14-16
1.5-2.5
3.5-6.0
M6 screw
8.0-10
14-16
22-25
Use a plus or minus screwdriver to loose or tighten screws.
Screw size
M3.5 screw
M4 screw
M5 screw
M6 screw
M4 screw (grounding terminal)
M5 screw (grounding terminal)
Refer to section 2.3.1 for details about terminal functions.
Manufacturer and Type-Form
Lug connector
Insulated Tube
JST
SHINAGAWA SHOKO
V2-M3
V2-4
V5.5-4
V2-5
V5.5-5
R8-5
TCM-81
R14-5
TCM-141
V2-6
R5.5-6
TCM-53
R8-6
TCM-81
R14-6
TCM-141
R22-6
TCM-221
Tightening torque
1.0 N  m
8.9 lb  in
1.4 N  m
12.4 lb  in
2.4 N  m
20.8 lb  in
4.5 N  m
40.0 lb  in
1.4 N  m
12.4 lb  in
2.8 N  m
24.8 lb  in
A-13
E6581611
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents