Toshiba VF-S15 Instruction Manual page 100

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

Note 1: If the load applied to the inverter 150% or more of its rated load or the operation frequency is 0.1Hz or
Note 2: The inverter is default setting so that, if the inverter becomes overloaded, it will automatically reduce the
Note 3: Overload detection level is variable by condition of output frequency and carrier frequency.
Note 4: Regarding to characteristic for aul=2 setting, refer to section 5.6.5).
4) Electronic thermal memory f632
When the power is OFF, it is possible to reset or maintain the overload totaling level.
This parameter's settings are applied both to the motor's electronic thermal memory and the electronic
thermal memory for inverter protection.
[Parameters settings]
Title
f632
● f632=1 is a function for complying with the U.S. NEC standards.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
less, the inverter may trip (ol1 or oc1 to oc3) in a shorter time.
carrier frequency to avoid an overload trip (ol1 or oc1 to oc3). A reduction in carrier frequency
causes an increase in noise from the motor, but this does not affect the performance of the inverter.
If you do not want the inverter to reduce the carrier frequency automatically, set the parameter
f316=0.
Function
Electronic thermal memory
Adjustment range
0: Disabled (thr, f173)
1: Enabled (thr, f173)
2: Disabled (thr)
3: Enabled (thr)
E-13
E6581611
5
Default setting
