(2) [f105 = 1 (Stop)]: If an F command and an R command are entered simultaneously,
6.6.2
f107 : Analog input terminal selection (VIB)
[Parameter setting]
● f107=0 : Input 0 to +10Vdc to VIB-CC terminals.
● f107=1 : Input -10 to +10Vdc to VIB-CC terminals.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
the motor will deceleration stop.
Output frequency [Hz]
Setting frequency
0
Forward run command
Reverse run command
Changing the voltage range of VIB terminal
Function
This parameter allows you to choose the voltage signal input for the VIB terminal.
Title
Function
Analog input terminal
f107
selection (VIB)
Resolution is maximum 1/1000 between 0 to +10Vdc.
Resolution is maximum 1/2000 between -10 to +10Vdc.
Adjustment range
0: 0-+10V
1: -10-+10V
F-29
E6581611
Forward run
Time[s]
Reverse run
ON
OFF
ON
OFF
6
Default setting
0