1
Note:
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Operate in areas where ambient temperature ranges from -10°C to 60°C.
When using the inverter in locations with temperatures above 40°C, remove the protective label on the
top of the inverter and use the inverter with the output current reduced according to section 6.18.
[Position for measuring ambient temperature]
The inverter is a heat-emitting body. Make sure proper space and ventilation is provided when
installing in the cabinet.
Do not install in any location that is subject to large amounts of vibration.
If the inverter is installed near any of the equipment listed below, provide measures to insure against
errors in operation.
Resistors
Do not install in any location of high temperature, high humidity,
moisture condensation and freezing and avoid locations where
there is exposure to water and/or where there may be large
amounts of dust, metallic fragments and oil mist.
Do not install in any location where corrosive gases or grinding
fluids are present.
3cm
3cm
Measurement position
5cm
Measurement position
Note:
If the inverter is installed in a location that is subject to
vibration, anti-vibration measures are required. Please
consult with Toshiba about these measures.
Solenoids:
Brakes:
Magnetic contactors: Attach surge suppressor on coil.
Fluorescent lights:
Resistors:
A-30
E6581611
Attach surge suppressor on coil.
Attach surge suppressor on coil.
Attach surge suppressor on coil.
Place far away from the inverter.