Toshiba VF-S15 Instruction Manual page 195

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

5) Adjusting feedback input
Make adjustment by converting input level of the feedback amount into frequency. Refer to section 6.10.2 for
details.
Example of 0 - 10 Vdc voltage input
setting

(60Hz)

(0Hz)
0V

0%
6) Setting the time elapsed before PID control starts
Waiting time until starting PID control system can be set to avoid PID control until the control system
becomes stable.
The inverter ignores feedback input signals, carries out operation at the frequency determined by the
frequency command value for the period of time specified with f359, and enters the PID control mode
after the elapsed time.
7) PID control forward/reverse characteristic switch
PID input characteristics can be reversed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Example of 0 - 10 Vdc voltage input
setting
10V

100%
VIA input value
Process quantity
Feedback amount
When characteristic is reversed according to parameters, set PID calculation reverse selection parameter
f380 is 1: Set reverse characteristics.
When characteristic is reversed using logic input terminal, assign function number 54/55, PID
characteristics switching, to an input terminal.
Note) If reverse characteristics is selected for parameter f380 and terminal input at the same time,
they become forward characteristic.
13
(60Hz)
11
(0Hz)
0V
5V
10
12
0%
100%
VIB input value
Opposite characteristic
×(-1)
Original characteristic
Characteristic selection (parameter or terminal input)
F-83
E6581611
Example of 4 - 20 mAdc voltage input
setting
19
(60Hz)
17
4mA
(0Hz)
16
20%
VIC input value
Output
PID
20mA
18
100%
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents