Toshiba VF-S15 Instruction Manual page 44

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note:
1
 Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Voltage class
Three-phase
240V class
Single-phase
240V class
Three-phase
500V class
Note 1) Case of 100% Load Continuation operation. The heat loss for the optional external devices (input AC
Note 2) It is power consumption when power is on but is not output (0Hz), and cooling fan is activated (model
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.
Calorific values (W)
Inverter type
4kHz
35
2004PM-W
45.6
2007PM-W
81
2015PM-W
94.9
2022PM-W
VFS15-
139
2037PM-W
2055PM-W
256
2075PM-W
305
2110PM-W
475
2150PM-W
557
2002PL-W
23
2004PL-W
37
VFS15S-
2007PL-W
46
2015PL-W
79
2022PL-W
101
30
4004PL-W
39
4007PL-W
58
4015PL-W
77
4022PL-W
VFS15-
131
4037PL-W
4055PL-W
211
4075PL-W
254
4110PL-W
387
4150PL-W
466
reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table
with cooling fan).
Amount of forcible air
cooling ventilation
Note 1)
3
required (m
/min)
12kHz
4kHz
12kHz
40
0.20
0.23
50
0.26
0.28
92
0.46
0.52
104
0.54
0.59
154
0.79
0.87
1.45
1.61
283
1.73
2.08
367
2.70
3.05
538
3.16
628
3.56
24.8
0.13
0.14
42.2
0.21
0.24
50
0.26
0.28
0.45
0.51
90
110
0.58
0.62
0.17
0.22
39
0.22
0.28
50
0.33
0.43
76
102
0.44
0.58
156
0.75
0.88
263
1.20
1.49
346
1.44
1.96
470
2.20
2.67
2.65
3.25
572
A-32
E6581611
Heat discharge
Standby
surface area required
power
for sealed storage
requirement
3
cabinet (m
)
(W)
Note 2)
4kHz
12kHz
0.70
0.80
6
0.91
0.99
6
1.61
1.85
10
1.90
2.07
10
2.77
3.08
11
5.12
5.66
22
6.10
7.34
22
9.50
10.76
31
11.14
12.56
31
0.46
0.50
5
0.74
0.84
5
0.92
1.00
5
1.57
1.80
8
2.03
2.20
8
0.61
0.78
12
0.78
1.00
12
1.15
1.53
12
1.53
2.04
13
2.63
3.12
13
4.22
5.26
22
5.08
6.92
22
7.74
9.40
31
9.32
11.44
31