Toshiba VF-S15 Instruction Manual page 139

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

6.5.3
f101 : Speed reach setting frequency
f102 : Speed reach detection band
[Parameter setting]
Parameter setting of frequency and detection band
Parameter setting of output terminal selection
Setting value 9 is reverse signal.
Note: Set f132 to assign to FLA-FLC-FLB terminals and f130 to RY-RC terminal.
If the detection band value + the set frequency is less than the designated frequency
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Output of set frequency speed reach signal
 Function
When the output frequency becomes equal to the frequency set by f101f102, an ON or OFF
signal is generated.
Title
Function
f101
Speed reach setting frequency
f102
Speed reach detection band
Title
Function
Output terminal
f131
selection 2A (OUT)
Output frequency [Hz]
 + 
 - 
Set frequency attainment signal
: OUT-NO terminals
Inversion of set frequency
attainment signal
Adjustment range
0.0-fh (Hz)
0.0-fh (Hz)
Adjustment range
0-255
(Refer to section 11.7.)

0
F-27
E6581611
Default setting
0.0
2.5
Setting
8: RCHF (Set frequency attainment
signal)
Time [s]
ON
OFF
ON
OFF
6