Toshiba VF-S15 Instruction Manual page 80

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

4.3.2
typ : Default setting
 Function
It is possible to return groups of parameters to their defaults, clear run times, and record/recall set
parameters.
[Parameter setting]
Title
4
typ
● This function will be displayed as 0 during reading on the right. This previous setting is displayed
Example: 3
● typ cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
50 Hz default setting (typ=1)
Setting typ to 1 sets the following parameters for base frequency 50 Hz use.
(The setting values of other parameters are not changed.)
• Maximum frequency (fh)
• Base frequency 1 (vl)
• VIA input point 2 frequency (f204) : 50Hz
• VIC input point 2 frequency (f219) : 50Hz
• Process upper limit (f367)
• Motor rated speed (f417)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Return to default settings
Function
Default setting
0
Adjustment range
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8: Load user setting parameters
9: Cumulative fan operation time
record clears
10, 11: -
12: Number of starting clear
13: Default setting 2 (complete
initialization)
: 50Hz
• Upper limit frequency (ul)
: 50Hz
• Base frequency 2 (f170)
• VIB input point 2 frequency (f213) : 50Hz
• Automatic light-load high-speed operation
: 50Hz
frequency (f330)
-1
: 1410 min
• Communication command point 2 frequency
(f814)
D-10
E6581611
Default setting
0
on the
left.
: 50Hz
: 50Hz
: 50Hz
: 50Hz