Trip
User Prog Trip

Trip generated by an onboard user program

This trip can be initiated from within an onboard user program using a function call which defines the sub-trip number.
96
Recommended actions:
Check the user program
User Save

User Save error / not completed

The User Save trip indicates that an error has been detected in the user save parameters saved in non-volatile memory.
For example, following a user save command, If the power to the drive was removed when the user parameters were being
saved.
36
Recommended actions:
Perform a user save in Pr mm.000 to ensure that the trip doesn't occur the next time the drive is powered up.
Ensure that the drive has enough time to complete the save before removing the power to the drive.
User Trip

User generated trip

These trips are not generated by the drive and are to be used by the user to trip the drive through an application program.
40 -89
Recommended actions:
112 -159
Check the user program
Volts Range

Supply voltage out of range detected in Regen mode

The Volts Range trip is initiated, if the Regen Minimum Voltage (03.026) is set to a non-zero value and the supply voltage is
outside the range defined by Regen Maximum Voltage (03.027) and Regen Minimum Voltage (03.026) for more than 100
ms.
Recommended actions:
169
Ensure the supply voltage is operating within the drive specification.
Ensure Pr 03.026 and Pr 03.027 are set correctly
Check the supply voltage waveform using an oscilloscope
Reduce the level of supply disturbance
Set Maximum Voltage (03.027) to zero to disable the trip.
Watchdog
Control word watchdog has timed out
The Watchdog trip indicates that the control word has been enabled and has timed out
30
Recommended actions:
274
Electrical
Getting
Basic
installation
started
parameters
the motor
Running
NV Media Card
Optimization
Operation
Diagnosis
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Unidrive M702 User Guide
UL listing
information
Issue Number: 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents