OHt Rectifier

Rectifier over temperature

The OHt Rectifier indicates that a rectifier over-temperature has been detected. The thermistor location can be identified
from the sub-trip number.
Source
Power
system
Recommend actions:
102
Check the motor and motor cable insulation with an insulation tester
Fit an output line reactor or sinusoidal filter
Force the heatsink fans to run at maximum speeds by setting Pr 06.045 = 11
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Decrease acceleration / deceleration rates
Reduce duty cycle
Reduce motor load
OI ac

Instantaneous output over current detected

The instantaneous drive output current has exceeded above VM_DRIVE_CURRENT_MAX.
Source
Control
system
Power
system
3
Recommended actions:
Acceleration/deceleration rate is too short
If seen during auto-tune reduce the voltage boost
Check for short circuit on the output cabling
Check integrity of the motor insulation using an insulation tester
Check feedback device wiring
Check feedback device mechanical coupling
Check feedback signals are free from noise
Is motor cable length within limits for the frame size
Reduce the values in the speed loop gain parameters - (Pr 03.010, 03.011, 03.012) or (Pr 03.013, 03.014, 03.015)
Has the phase angle autotune been completed? (RFC-S mode only)
Reduce the values in current loop gain parameters (RFC-A, RFC-S modes only)
OI Brake
Braking IGBT over current detected: short circuit protection for the braking IGBT activated
The OI Brake trip indicates that over current has been detected in braking IGBT or braking IGBT protection has been
activated.
Source
Power
4
system
Recommended actions:
Check brake resistor wiring
Check braking resistor value is greater than or equal to the minimum resistance value
Check braking resistor insulation
OI dc
Power module over current detected from IGBT on state voltage monitoring
The OI dc trip indicates that the short circuit protection for the drive output stage has been activated.
Recommended actions:
109
Disconnect the motor cable at the drive end and check the motor and cable insulation with an insulation tester
Replace the drive
Unidrive M702 User Guide
Issue Number: 3
Electrical
Getting
Basic
installation
started
parameters
the motor
xx
y
Power module
Rectifier
number
number
xx
y
Rectifier
00
number
Power
module
0
number
xx
y
Power
module
0
number
Running
NV Media Card
Optimization
Operation
Diagnosis
zz
zz
Thermistor location defined by zz
zz
Instantaneous over-current trip when the measured AC current
00
exceeds VM_DRIVE_CURRENT[MAX].
zz
00
Braking IGBT instantaneous over-current trip
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Description
Description
Description
UL listing
information
263

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents