Phase Offset Incorrect While Running; Feedback Device Comms Failure; Checksum Or Crc Error; Encoder Has Indicated An Error - Emerson Unidrive M702 User Manual

Universal variable speed ac drive for induction and permanent magnetmotors
Hide thumbs Also See for Unidrive M702:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Trip
Encoder 3

Phase offset incorrect while running

The Encoder 3 trip indicates that the drive has detected an incorrect UVW phase angle while running (RFC-S mode only) or
SINCOS phase error. The feedback device which has caused the trip can be identified by the sub-trip number.
Sub-trip
Recommended actions:
191
Check encoder shield connections
Ensure the encoder cable is one uninterrupted cable
Check the encoder signal for noise with an oscilloscope
Check the integrity of the encoder mechanical mounting
For a UVW servo encoder, ensure that the phase rotation of the UVW commutation signals is the same as
the phase rotation of the motor
For a SINCOS encoder, ensure that motor and incremental SINCOS connections are correct and that for forward
rotation of the motor, the encoder rotates clockwise (when looking at the shaft of the encoder)
Repeat the offset measurement test
Encoder 4

Feedback device comms failure

The Encoder 4 trip indicates that the encoder communications has timed out or the communications position
message transfer time is too long. This trip can also be caused due to wire break in the communication channel between
the drive and the encoder. The feedback device which has caused the trip can be identified by the sub-trip number.
Sub-trip
192
Recommended actions:
Ensure the encoder power supply setting (Pr 03.036) is correct
Complete encoder auto-configuration (Pr 03.041)
Check the encoder wiring
Replace the feedback device
Encoder 5

Checksum or CRC error

The Encoder 5 trip indicates that there is a checksum or CRC error, or the SSI encoder is not ready. The Encoder 5 trip can
also indicate a wire break to a communications based encoder.
Sub-trip
Recommended actions:
193
Check the encoder cable shield connections
Ensure the cable is one uninterrupted cable - remove any connector blocks or if unavoidable minimise the length of any
shield pigtails to the connector block
Check the encoder signal for noise with an oscilloscope
Check the comms resolution setting (Pr 03.035)
If using a Hiperface, EnDat encoder or BiSS encoder carry out an encoder auto-configuration (Pr 03.041 = Enabled)
Replace the encoder
Encoder 6

Encoder has indicated an error

The Encoder 6 trip indicates that the encoder has indicated an error or that the power supply has failed to an SSI encoder.
The Encoder 6 trip can also indicate a wire break to an SSI encoder.
Sub-trip
194
Recommended actions:
For SSI encoders, check the wiring and encoder power supply setting (Pr 03.036)
Replace the encoder / contact the supplier of the encoder
Unidrive M702 User Guide
Issue Number: 3
Electrical
Getting
Basic
installation
started
parameters
1
Drive position feedback interface 1
2
Drive position feedback interface 2
1
Drive position feedback interface 1
2
Drive position feedback interface 2
1
Drive position feedback interface 1
2
Drive position feedback interface 2
1
Drive position feedback interface 1
2
Drive position feedback interface 2
Running
NV Media Card
Optimization
the motor
Operation
Diagnosis
Reason
Reason
Reason
Reason
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
UL listing
information
255

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents