Absolute Sincos encoder with Hiperface or EnDat serial communication, or
Absolute EnDat communication only encoder or BiSS encoder
Device Type (03.038)
Supply Voltage (03.036)
Auto-configuration Select (03.041)
Comms Baud Rate (03.037)
Error Detection Level (03.040)
Absolute SSI communications only encoder, or Absolute Sincos encoder with SSI communications
Device Type (03.038)
Supply Voltage (03.036)
Rotary Line Per Revolution (03.034)
SSI Binary Mode (03.048)
Rotary Turns Bits (03.033)
Comms Bits (03.035)
Comms Baud Rate (03.037)
Error Detection Level (03.040)
UVW commutation signal only encoders*
Device Type (03.038)
Supply Voltage (03.036)
Error Detection Level (03.040)
* This feedback device provides very low resolution feedback and should not be used for applications requiring a high level of performance.
Due to the low resolution of UVW communication only encoders, it is recommended that the P1 Feedback Filter (03.042) is set to its maximum value.
A value of 1 ms to 2 ms may also be required in the Current Demand Filter (04.012) and it is also recommended that the speed loop gains are set to
a low value to obtain stable operation.
Unidrive M702 User Guide
Issue Number: 3
Electrical
Getting
Basic
installation
started
parameters
the motor
SC Hiperface (7) for a Sincos encoder with Hiperface serial communications
EnDat (8) for an EnDat communications only encoder
SC EnDat (9) for a Sincos encoder with EnDat serial communications
BiSS (13) for a BiSS communication only encoder
5 V (0), 8 V (1) or 15 V (2)
Auto-configuration is enabled at default and automatically sets up the following parameters.
Rotary Turns Bits (03.033)
Rotary Lines Per Revolutions (03.034)
Comms Bits (03.035)
These parameters can be entered manually when Pr 03.041 is set to Disabled (0).
100 k, 200 k, 300 k, 400 k, 500 k, 1 M, 1.5 M, 2 M, 4 M
Bit
3
2
1
0
x
x
x
1
Enable wire break detection
x
x
1
x
Enable phase error detection
1
x
x
x
Disable trips Encoder 1 to Encoder 7
So for example, to enable the wire break and phase error detection, set Pr 03.040 to 0011.
SSI (10) for a SSI communications only encoder
SC SSI (11) for a Sincos encoder with SSI serial communications
5 V (0), 8 V (1) or 15 V (2)
Set the number of sine waves per revolution of the encoder
Off = Gray Code
On = Binary Mode
Set to the number of turns bits for the encoder (this is normally 12 bits for a SSI encoder)
Total number of bits of position information (this is usually 25 bits for a SSI encoder)
100 k, 200 k, 300 k, 400 k, 500 k, 1 M, 1.5 M, 2 M, 4 M
Bit
3
2
1
0
x
x
x
1
Enable wire break detection
x
x
1
x
Enable phase error detection
x
1
x
x
Enable SSI power supply alarm bit monitor
1
x
x
x
Disable trips Encoder 1 to Encoder 7
So for example, to enable the wire break and phase error detection, set Pr 03.040 to 0011.
Commutation Only (16) for a quadrature encoder with commutation signals*
5 V (0), 8 V (1) or 15 V (2)
Set to zero to disable wire break detection
Running
NV Media Card
Optimization
Operation
Description
Description
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
UL listing
information
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents