Emerson Unidrive M702 User Manual page 85

Universal variable speed ac drive for induction and permanent magnetmotors
Hide thumbs Also See for Unidrive M702:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Z, Data, Freeze, Ref H
5
Z\, Data\, Freeze\, Ref L
6
AB (0), FD (1), FR (2), AB Servo (3), FD Servo(4), FR Servo (5
SC SC (15)
Type
Maximum input frequency
Line loading
Line termination components
Working common mode range
SC Hiperface (7), SC EnDat (9), SC SSI (11), SC Servo (12)
Type
Maximum input frequency
Line loading
Line termination components
Working common mode range
EnDat (8), SSI (10), BiSS (13
)
Type
Maximum input frequency
Line loading
Line termination components
Working common mode range
Resolver (14)
Type
Nominal voltage
Operating frequency
Line loading
Common to All
Absolute maximum applied voltage relative to 0V -9 V to 14 V
Unidrive M702 User Guide
Issue Number: 3
Electrical
Getting
Basic
installation
started
parameters
the motor
EIA 485 differential receivers
512 kHz
120 Ω (switchable)
–7 V to +12 V
EIA 485 differential receivers
4 MHz
120 Ω (switchable)
–7 V to +12 V
EIA 485 differential receivers
4 MHz
120 Ω (switchable)
–7 V to +12 V
Differential voltage
0 – 2 Vrms depending on turns
ratio
6 - 8 KHz
Running
NV Media Card
Optimization
Operation
U, C, Not used, Not used
7
U\, C\, Not used, Not used
8
),
AB Servo (3), FD Servo(4), FR Servo (5
Type
Maximum input frequency
Line loading
Line termination components
Working common mode range
SC SC (15)
Type
Maximum Signal level
Maximum input frequency
Maximum applied differential voltage and
common mode voltage range
EnDat (8), SSI (10), BiSS (13)
Not used
Resolver (14)
Not used
Common to All
Absolute maximum applied voltage relative to 0V -9 V to 14 V
V, D, Not used, Not used
9
V\, D\, Not used, Not used
10
AB Servo (3), FD Servo(4), FR Servo (5
Type
Maximum input frequency
Line loading
Line termination components
Working common mode range
SC SC (15)
Type
Maximum Signal level
Maximum input frequency
Maximum applied differential voltage and
common mode voltage range
EnDat (8), SSI (10), BiSS (13)
Not used
Resolver (14)
Not used
Common to All
Absolute maximum applied voltage relative to 0V -9 V to 14 V
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
),
SC Servo (12)
EIA 485 differential receivers
512 kHz
120 Ω (switchable)
–7 V to +12 V
Differential voltage
1.25 V peak to peak (sin with
regard to sinref and cos with
regard to cosref)
See Table 4-30
±4 V
),
SC Servo (12)
EIA 485 differential receivers
512 kHz
120 Ω (switchable)
–7 V to +12 V
Differential voltage
1.25 V peak to peak (sin with
regard to sinref and cos with
regard to cosref)
See Table 4-30
±4 V
UL listing
information
85