The Load On The Drive Has Fallen Below The Low Load Detection Level; Output Current Overload Timed Out; Electronic Nameplate Transfer Has Failed; Control Stage Over Temperature - Emerson Unidrive M702 User Manual

Universal variable speed ac drive for induction and permanent magnetmotors
Hide thumbs Also See for Unidrive M702:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Trip
Low Load

The load on the drive has fallen below the low load detection level

When the low load detector is active, the low load condition is detected when the Percentage Load (Pr 04.020) falls below
the threshold defined by the Low Load Detection Level (Pr 04.027).
Enable Trip On Low Load (Pr 04.029) defines the action taken when low load is detected. If Enable Trip On Low Load
38
(Pr 04.029) = 0, a Low Load warning is displayed and Low Load Detected Alarm (Pr 10.062) = 1. If Enable Trip On Low
Load (Pr 04.029) = 1 no warning is given, but a Low Load trip is initiated.
Recommended actions:
Check the load on the motor has not changed
Motor Too Hot
Output current overload timed out (I
The Motor Too Hot trip indicates a motor thermal overload based on the output current (Pr 05.007) and motor thermal time
constant (Pr 04.015). Pr 04.019 displays the motor temperature as a percentage of the maximum value. The drive will trip
on Motor Too Hot when Pr 04.019 gets to 100 %.
Recommended actions:
Ensure the load is not jammed / sticking
20
Check the load on the motor has not changed
If seen during an auto-tune test in RFC-S mode, ensure the motor rated current in Pr 05.007 is ≤ Heavy duty current
rating of the drive
Tune the rated speed parameter (RFC-A mode only)
Check feedback signal for noise
Ensure the motor rated current is not zero
Name Plate

Electronic nameplate transfer has failed

The Name Plate trip is initiated if an electronic name plate transfer between the drive and the motor has failed. The exact
reason for the trip can be identified from the sub-trip number.
Recommended actions:
176
Ensure that the correct data is stored in the encoder by re-transferring the required data from drive into the encoder.
Enter the motor nameplate parameters manually
Replace the feedback device
OHt Brake
Braking IGBT over-temperature
The OHt Brake over-temperature trip indicates that braking IGBT over-temperature has been detected based on software
thermal model.
101
Recommended actions:
Check braking resistor value is greater than or equal to the minimum resistance value
OHt Control

Control stage over temperature

This OHt Control trip indicates that a control stage over-temperature has been detected. From the sub-trip 'xxyzz', the
Thermistor location is identified by 'zz'.
Control system
Control system
Control system
23
Recommended actions:
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Reduce the drive switching frequency
Check ambient temperature
Unidrive M702 User Guide
Issue Number: 3
Electrical
Getting
Basic
installation
started
parameters
the motor
Source
xx
00
00
00
Running
NV Media Card
Optimization
Operation
Diagnosis
2
t)
y
zz
0
01
Control board thermistor 1 over temperature
0
02
Control board thermistor 2 over temperature
0
03
I/O board thermistor over temperature
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Description
UL listing
information
261