Weights; Input Current, Fuse And Cable Size Ratings - Emerson Unidrive M702 User Manual

Universal variable speed ac drive for induction and permanent magnetmotors
Hide thumbs Also See for Unidrive M702:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
12.1.19

Weights

Table 12-12 Overall drive weights
Size
Model
034300078, 034300100
3
All other variants
4
All variants
5
All variants
6
All variants
7
All variants
8
12.1.20
SAFE TORQUE OFF data
Data as verified by TÜV Rheinland:
According to EN ISO 13849-1:
PL = e
Category = 4
MTTF
= High
D
DC
= High
av
Mission Time and Proof Test Interval = 20 years
The calculated MTTF
for the complete STO function is:
D
STO1 2574 yr
STO2 2716 yr
According to EN 61800-5-2:
SIL = 3
-11
-1
PFH = 4.21 x 10
h
Logic levels comply with IEC 61131-2:2007 for type 1 digital inputs rated
at 24 V. Maximum level for logic low to achieve SIL3 and PL e 5 V and
0.5 mA.
12.1.21

Input current, fuse and cable size ratings

The input current is affected by the supply voltage and impedance.
Typical input current
The values of typical input current are given to aid calculations for power
flow and power loss.
The values of typical input current are stated for a balanced supply.
Maximum continuous input current
The values of maximum continuous input current are given to aid the
selection of cables and fuses. These values are stated for the worst case
condition with the unusual combination of stiff supply with bad balance.
The value stated for the maximum continuous input current would only
be seen in one of the input phases. The current in the other two phases
would be significantly lower.
The values of maximum input current are stated for a supply with a 2 %
negative phase-sequence imbalance and rated at the maximum supply
fault current given in Table 12-13.
Table 12-13 Supply fault current used to calculate maximum input currents
Model
All
Unidrive M702 User Guide
Issue Number: 3
Electrical
Getting
Basic
installation
started
parameters
kg
lb
4.5
9.9
4.0
8.8
6.5
14.30
7.4
16.30
14
30.90
28
61.70
Symmetrical fault level (kA)
100
Running
NV Media Card
Optimization
the motor
Operation
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
UL listing
information
237

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents