Output Adjustment Functions
Note

4-16-3 MV at PV Error

Position-proportional Models
Open, close, or hold status can be selected for floating control or when the
Direct Setting of Position Proportional MV parameter is set to OFF. With open
status, only the open output will turn ON. With close status, only the close out-
put will turn ON. With hold status, the open and close outputs will both turn
OFF. The default is for hold status, i.e., no outputs. With close status, only the
close output will turn ON. With hold status, the open and close outputs will
both turn OFF. The default setting is for hold status, with no outputs.
If the Direct Setting of Position Proportional MV parameter is set to ON during
close control, the valve opening can be specified. The default setting is 0.0
(i.e., the open and close outputs are adjusted so that valve opening will be 0).
Parameter
name
MV at Reset
5.0 to 105.0 for standard control
(mv-r)
105.0 to 105.0 (heating/cooling control)
Position-proportional Control
Close control and Direct Setting of Posi-
tion Proportional MV parameter ON: 5.0
to 105.0
Floating control or Direct Setting of Posi-
tion Proportional MV parameter OFF:
CLOS (Control output 2 ON)
HOLD (Control outputs 1 and 2 both
OFF)
OPEN (Control output 1 ON)
The order of priority is as follows: Manual MV > MV at reset > MV at error.
• The following table shows the operation when a potentiometer error
occurs when the Direct Setting of Position Proportional MV parameter is
set to ON.
MV at reset
MV at reset
When the MV at reset is not one of the above values, the open and
close outputs will both be OFF.
• A fixed MV is output for an input error, RSP input error, or potentiometer
error (close control only). To set the MV at error, set the MV at Reset and
Error Addition parameter (advanced function setting level) to ON.
In reset status, the setting of the MV at Reset parameter takes priority.
With manual operation, the manual MV takes priority.
Standard Models
With heating/cooling control, the MV on the cooling side is taken to be a neg-
ative value, so the output is made to the heating side for a positive value and
to the cooling side for a negative value. The default setting is 0.0 (i.e., there
are not outputs for either standard control or heating/cooling control).
Setting range
100
Open output ON
0
Close output ON
Section 4-16
Unit
Default
% or none
0.0 or HOLD