Advanced Function Setting Level
Direct Setting of Position
pmvd
Proportional MV
Function
Setting
See
See
pvrp
PV Rate of Change Calculation Period
Function
Setting
See
See
282
• When this parameter is set to ON, valve opening can be specified in the
MV at Reset, MV at PV Error, and Manual MV Limit Enable parameters.
on: Enabled, off: Disabled
■ Related Parameters
MV at reset, MV at error (adjustment level): Page 220
MV at PV error (adjustment level): Page 220
Manual MV (manual control level): Page 232
• The change width can be found for PV input values in any set period. Dif-
ferences with previous values in each set period are calculated, and an
alarm is output if the results exceed the alarm value.
• The PV rate of change calculation period can be set in units of 60 ms
(sampling period).
Setting range
1 to 999
■ Related Parameters
Process value, Process value/set point (operation level): Page 185
Alarm 1 to 3 type, (Initial setting level): Pages 240, 244, 245.
Close control (position-proportional
models) must be used.
Setting range
Alarms 1, 2, and 3 must be assigned.
The alarm type must be set to 13.
Unit
Sampling period
Section 5-10
Default
OFF
Default
17 (= 17
60 ms = 1020 ms)