Wiring Terminals
E5AN/EN-HT
The default setting is for a K-type thermocouple
(input type = 5). If a different sensor is used, an
input error (s.err) will occur. Check the setting of
the Input Type parameter.
100 to 240 VAC
24 VAC/VDC (no polarity)
Input power
supply
Control output 1
Control output 2
Auxiliary output 2
Auxiliary output 1
Control outputs 1, 2
Control Output Unit
Control outputs 1, 2
Refer to page 32
Models with Position-
proportional Control
Relay output
250 VAC, 1 A
(including inrush
current)
Auxiliary outputs 1, 2, 3
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
32
Event Inputs
1
21
11
(See note.)
EV2
2
22
12
EV1
3
23
13
CT2
4
24
14
CT1
25
5
15
CT2
6
26
16
DO NOT
7
27
17
USE
DO NOT
8
28
18
USE
29
9
19
10
20
30
Note: When there are two event inputs, they use EV3 and EV4.
Control Output Unit
1
Input power
supply
2
3
Output unit
4
5
Output unit
6
7
Auxiliary output 2
8
9
Auxiliary output 1
10
Note Wire all voltage input terminals correctly. The Digital Controller may
fail if the voltage input terminals are wired incorrectly.
Control outputs that are voltage outputs are not isolated from the internal circuits.
When using a grounded thermocouple, do not connect any of the control output ter-
minals to ground. (If both are grounded, measurements will be unreliable due to
sneak current.)
Communications
E53-EN01
RS-232C
S D
11
11
RD
12
12
S G
13
13
DO NOT USE
21
21
DO NOT USE
22
22
Potentiometer
14
O
15
Auxiliary output 3
W
16
C
DO N OT
DO NOT
U SE
USE
A
DO NOT
USE
V
mA
B
B
DO NOT
DO NOT
USE
USE
Models with Position-
proportional Control
1
Input power
supply
2
3
Open
4
5
Closed
6
DO NOT USE
7
Transfer output
Auxiliary output 2
8
9
Remote SP input
Auxiliary output 1
1 0
Note: Terminals 21 to 30 exist only on the following models.
Models with four event inputs (E5@N-@BB@@)
Models with a transfer output (E5@N-@F@)
Section 2-2
E53-EN03
E53-EN02
RS-485
RS-422
B ( )
RDB
11
RDA
A ( )
12
SG
DO NOT USE
13
B ( )
S DB
21
S DA
A ( )
22
Auxiliary output 3
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, input error, or Remote
SP Input Error is sent to the
output to which the alarm 1
function is assigned.
Event input/
Transfer output/
Remote SP
(See note.)
21
22
23
EV3
24
EV4
25
26
27
4 to 20 mA DC
(Load: 600
28
29
4 to 20 mA DC
30
max.)