Advertisement

Advanced Function Setting Level
inf
Input Digital Filter
Function
Setting
pvad
Additional PV Display
Function
Setting
o-dp
MV Display
Function
Setting
262
• This parameter sets the time constant for the input digital filter. The follow-
ing diagram shows the effect on data after passing through the digital fil-
ter:
PV before passing through filter
A
(Time
constant)
Input digital filter
Setting range
Unit
0.0 to 999.9
Second
This parameter adds a display at the beginning of the operation level for the
process value (PV). If there is no need to display the set point, use this to dis-
play only the present temperature.
Set to ON to display, and OFF to not display.
Setting range
on: Displayed, off: Not displayed
This parameter is used to display the manipulated variable (MV).
The manipulated variable is displayed when the MV Monitor (Heating) and MV
Monitor (Cooling) parameters are set to ON, and not displayed when these
parameters are set to OFF.
Setting range
on: Displayed, off: Not displayed
PV after passing through filter
0.63 A
Time
Default
0.0
Default
off
Default
off