Omron E5CN-HT User Manual page 258

Digital controllers programmable type
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

Initial Setting Level
in-t
Input Type
Function
Setting
Input type
Specifications
Platinum resistance
Pt100
thermometer
JPt100
Thermocouple
K
J
T
E
L
U
N
R
S
B
W
PLII
K
J
T
Platinum resistance
Pt100
thermometer
Current input
4 to 20 mA
0 to 20 mA
Voltage input
1 to 5 V
0 to 5 V
0 to 10 V
See
See
236
• This parameter sets the type of sensor.
• When this parameter is changed, the set point limiter is changed to the
defaults. If the limiter must be specified, set the SP Upper Limit and SP
Lower Limit parameters (initial setting level) again.
• Set one of the set values from the following table.
The default is 5.
• If a platinum resistance thermometer is mistakenly connected while a set-
ting for other than a platinum resistance thermometer is in effect, S.ERR
will be displayed. To clear the S.ERR display, check the wiring and then
cycle the power.
Set value
0
200.0 to 850.0 ( C)/ 300.0 to 1,500.0 ( F)
1
199.9 to 500.0 ( C)/ 199.9 to 900.0 ( F)
2
0.0 to 100.0 ( C)/0.0 to 210.0 ( F)
3
199.9 to 500.0 ( C)/ 199.9 to 900.0 ( F)
4
0.0 to 100.0 ( C)/0.0 to 210.0 ( F)
5
200.0 to 1,300.0 ( C)/ 300.0 to 2,300.0 ( F)
6
20.0 to 500.0 ( C)/0.0 to 900.0 ( F)
7
100.0 to 850.0 ( C)/ 100.0 to 1,500.0 ( F)
8
20.0 to 400.0 ( C)/0.0 to 750.0 ( F)
9
200.0 to 400.0 ( C)/ 300.0 to 700.0 ( F)
10
199.9 to 400.0 ( C)/ 199.9 to 700.0 ( F)
11
200.0 to 600.0 ( C)/ 300.0 to 1,100.0 ( F)
12
100.0 to 850.0 ( C)/ 100.0 to 1,500.0 ( F)
13
200.0 to 400.0 ( C)/ 300.0 to 700.0 ( F)
14
199.9 to 400.0 ( C)/ 199.9 to 700.0 ( F)
15
200.0 to 1,300.0 ( C)/ 300.0 to 2,300.0 ( F)
16
0.0 to 1,700.0 ( C)/0.0 to 3,000.0 ( F)
17
0.0 to 1,700.0 ( C)/0.0 to 3,000.0 ( F)
18
100.0 to 1,800.0 ( C)/300.0 to 3,200.0 ( F)
19
0.0 to 2,300.0 ( C)/0.0 to 3,200.0 ( F)
20
0.0 to 1,300.0 ( C)/0.0 to 2,300.0 ( F)
21
50.0 to 200.0 ( C)/ 50.0 to 200.0 ( F)
22
50.0 to 200.0 ( C)/ 50.0 to 200.0 ( F)
23
50.0 to 200.0 ( C)/ 50.0 to 200.0 ( F)
24
50.0 to 200.0 ( C)/ 50.0 to 200.0 ( F)
25
One of the following ranges depending on the scal-
ing.
26
19999 to 32400
27
1999.9 to 3240.0
28
199.99 to 324.00
19.999 to 32.400
29
■ Related Parameters
Temperature unit, Set point upper limit, Set point lower limit (initial setting
level): Page 237
Input temperature range
Section 5-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-htE5an-ht

Table of Contents